Pull Alarm Status w/o Data
This is useful to bring alarm status in without affecting the value stored in a record. In the following example the alarm status of $(P):set is fetched by $(P):rbv when it is processed, but the value is read from a different record.
record(bo, "$(P):set") { field(OSEV, "MAJOR") field(FLNK, "$(P):rbv") }
record(bi, "$(P):rbv") { field(SDIS, "$(P):set NPP MS") field(DISV, "-1") field(INP , "$(P):some:other:record") }
Combined Setting and Readback
Use when a single PV is desired. Could be used to show the results of rounding in a float to fixed precision conversion.
In the following example the value read from a ‘bi’ is inverted so that the associated ‘bo’ acts as a toggle.
record(bi, "$(P):rbv") { field(DTYP, "...") field(INP , "...") field(PINI, "YES") field(FLNK, "$(P):inv") }
record(calcout, "$(P):inv") field(CALC, "!A") field(INPA, "$(P):rbv") field(OUT , "$(P) NPP") }
record(bo, "$(P)") { field(DTYP, "...") field(OUT , "...") field(FLNK, "$(P):rbv") }
The important point is the NPP modifier on output link of the ‘calcout’ record. This updates the VAL field of the ‘bo’ record (and posts monitors) without processing it.